5.10 Changing operation panel display
5.10.1 Changing the unit (A/V) from a percentage of current
and voltage
f701
:Current/voltage unit selection
Function
These parameters are used to change the unit of monitor display.
%
A (ampere)/V (volt)
Current 100% = Rated current of inverter
Input/output voltage 100% = 200Vac (240V class), 400Vac (500V class)
■
Example of setting
During the operation of the VFS15-2015PM-W (rated current: 8.0A) at the rated load (100% load), units are
displayed as follows:
1) Display in percentage terms
2) Display in amperes/volts
[Parameter setting]
Title
Function
Adjustment range
Default setting
f701
Current/voltage unit
selection
0: %
1: A (ampere) / V (volt)
0
* The
f701
converts the following parameter settings:
A display : Current monitor display: Load current, torque current
Motor electronic-thermal protection level 1 & 2
,
f173
DC braking current
f251
Stall prevention level 1 & 2
f601
,
f185
Small current detection current
f611
V display : Input voltage, output voltage
Note) Base frequency voltage 1 & 2(
,
) always displayed in the unit of V.
Output current:
8.0A
Input voltage:
200V
Input voltage:
100%
Output current:
100%
%
%