E6581611
F-41
6
■
Adjustment with continuous signals (Operation example 1)
Set parameters as follows to adjust the output frequency up or down in proportion to the frequency
adjustment signal input time:
External logic input up/down frequency incremental gradient =
f265
/
f264
setting time
External logic input up/down frequency decremental gradient =
f267
/
f266
setting time
Set parameters as follows to adjust the output frequency up or down almost synchronously with the
adjustment by the external logic input up/down frequency command:
f264
=
f266
= 0.1
(
fh
/
acc
)
(
f265
/
f264
setting time)
(
fh
/
dec
)
(
f267
/
f266
setting time)
<<Sample sequence diagram 1: Adjustment with continuous signals>>
The dotted line denotes the output frequency obtained by combining the slowdown speed and the
panel frequency adjustment speed.
Frequency 0 Hz
Lower limit frequency
Gradient
f267
/
f266
Gradient
f265
/
f264
Upper limit frequency
DOWN signal
UP signal
Forward / reverse command
Set frequency clearing signal
■
Adjustment with pulse signals (Operation example 2)
Set parameters as follows to stepwise adjust the frequency by one pulse:
f264
,
f266
≤
Pulse On time
f265
,
f267
= Frequency obtained with each pulse
* The inverter does not respond to any pulses with an ON time shorter than that set with
f264
or
f266
. 12ms or more of clearing signal is allowed.
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......
Page 430: ......