E6581611
K-31
11
Table of input terminal functions 2
Function
No.
Code Function
Action
Reference
52
IDC
PID integral/differential clear
ON: Integral/differential clear, OFF: Clear canceled
6.24
53
IDCN
Inversion of PID integral/differential clear
Inversion of IDC
54
DR
PID characteristics switching
ON: Inverted characteristics of
selection
OFF: Characteristics of
selection
55
DRN
Inversion of PID characteristics switching
Inversion of DR
56
FORCE
Forced run operation
ON: Forced run operation if specified faults are occurred
(
frequency)
OFF: Normal operation
6.30
57
FORCEN Inversion of forced run operation
Inversion of FORCE
58
FIRE
Fire speed operation
ON: Fire speed operation (
frequency)
OFF: Normal operation
59
FIREN
Inversion of fire speed operation
Inversion of FIRE
60
DWELL
Acceleration/deceleration suspend signal
ON: Acceleration/deceleration suspend
OFF: Normal operation
6.23
61
DWELLN
Inversion of acceleration/deceleration
suspend signal
Inversion of DWELL
62
KEB
Power failure synchronized signal
ON: Deceleration stop with synchronizing when power failure
OFF: Normal operation
6.19.2
63
KEBN
Inversion of power failure synchronized signal
Inversion of KEB
64, 65
Factory specific coefficient
-
*1
70, 71
Factory specific coefficient
-
*1
74
CKWH
Integrating wattmeter(kWh) display clear
ON: Integrating wattmeter(kwh) monitor display clear
OFF: Disabled
6.36
75
CKWHN
Inversion of integrating wattmeter display clear
Inversion of CKWH
76
TRACE
Trace back trigger signal
ON: Trigger(start) signal
of trace function
OFF: Disabled
6.35
77
TRACEN Inversion of trace back trigger signal
Inversion of TRACE
78
HSLL
Light-load high-speed operation prohibitive
signal
ON: Light-load high-speed operation
prohibited
OFF: Light-load high-speed operation
permitted
6.21
79
HSLLN
Inversion of light-load high-speed operation
prohibitive signal
Inversion of HSLL
80
HDRY
Holding of RY-RC terminal output
ON: Once turned on, RY-RC are held on.
OFF: The status of RY-RC changes in real time according to
conditions.
7.2.2
81
HDRYN
Inversion of holding of RY-RC terminal output
Inversion of HDRY
82
HDOUT
Holding of OUT-NO terminal output
ON: Once turned on, OUT-NO are held on.
OFF: The status of OUT-NO changes in real time according
to conditions.
83
HDOUTN Inversion of holding of OUT-NO terminal output
Inversion of HDOUT
88
UP
Frequency UP
ON: Frequency increased
OFF: Frequency increase canceled
6.10.4
89
UPN
Inversion of frequency UP
Inversion of UP
90
DWN
Frequency DOWN
ON: Frequency decreased
OFF: Frequency decrease canceled
91
DWNN
Inversion of frequency DOWN
Inversion of DWN
92 CLR Clear
frequency
UP/DOWN
OFF
¤
ON: Clear frequency UP/DOWN
93
CLRN
Inversion of clear frequency UP/DOWN
Inversion of CLR
96
FRR
Coast stop command
ON: Coast stop (Gate OFF)
OFF: Coast stop canceled
3.1.1
6.34.8
97
FRRN
Inversion of coast stop command
Inversion of FRR
98 FR
Forward/reverse
selection
ON:
Forward
operation command
OFF: Reverse operation command
7.2.1
99
FRN
Inversion of forward/reverse selection
Inversion of FR
*1: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.