E6581611
F-130
6
6.34.6 Change display of the status monitor
f711
to
f718
: Status monitor 1 to 8
Change monitor display items in the status monitor mode.
⇒
Refer to chapter 8 for details.
6.34.7 Change the status monitor condition
f709
: Standard monitor hold function
f746
: Status monitor filter
•
Function
The standard monitor display can be hold.
Some status monitors can be filtered to display.
,
If
is set to
, the monitored values selected with
(standard monitor display selection
parameter) are displayed. For peak hold values and minimum hold values, the minimum values in each
operation cycle are displayed. When the motor is at a standstill, the values monitored last are held as they
were until the motor is started the next time.
The maximum and minimum values monitored after power is turned on is always displayed no matter
whether the motor is in operation or at a standstill.
The maximum and minimum values
are cleared to press the EASY key by setting
f750
to
3
.
,
“Output current”, “Input voltage”, “Output voltage” and “Torque” can be filtered by
f746
.
⇒
Refer to chapter 8 about status monitor.
[Parameter setting]
Title
Function
Adjustment range
Default setting
Standard monitor hold function
0: Real time
1: Peak hold
2: Minimum hold
0
f746
Status monitor filter
8-1000 (ms)
200
f750
EASY key function selection
0: Easy / standard setting mode switching
function
1: Shortcut key
2: Local / remote key
3: Monitor peak / minimum hold trigger
4: -
5: -
0