E6581611
F-126
6
When protecting a parameter is necessary with the external logic input terminal, set with the following method.
■
Prohibit changing parameters settings and reading parameters from logic input
Set "Parameter editing prohibition" or "Parameter reading/editing prohibition" for an input terminal.
Activating the "Parameter editing prohibited" function prevents changes to parameters.
Activating the "Parameter reading/editing prohibition" function prevents reads and writes to parameters.
The following table shows an example of setting input terminal S1 and S2.
Title
Function
Adjustment range
Setting
f114
Input terminal selection 4A
(S1)
0-203
200: PWP
(Parameter editing prohibition)
f115
Input terminal selection 5
(S2)
0-203
202: PRWP
(Parameter reading prohibition)
Setting value 201, 203 are reverse signal.
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......
Page 430: ......