E6581611
F-4
6
How to use the Application easy setting
1)
Choose the machine
Operation panel
action
LED display
Operation
0
0
Displays the output frequency.
(When standard monitor display selection
is set to
[output frequency])
auh
The first basic parameter “
auh
” (history function) is displayed.
aua
Turn the setting dial to the right to change the parameter to
aua
.
0
Set values are displayed by pressing the center of the setting dial.
2
Turn the setting dial to the right to select
1
or
2
.
2
aua
Press the center of the setting dial to save the changed set value.
aua
and the set value are displayed alternately.
2)
The parameters necessary to the machine are set to easy setting mode parameter 1-32. (Refer to the chart
bellow)
3)
Set the parameters using easy setting mode. Refer to section 4.2 for easy setting mode.
Table of parameters that can be set using
aua
1
: Initial
easy setting
2
:
Conveyor
3
: Material
handling
4
: Hoisting
5
: Fan
6
: Pump
7
:
Compressor
f751
cmod
cmod
cmod
cmod
cmod
cmod
cmod
f752
fmod
fmod
fmod
fmod
fmod
fmod
fmod
f753
acc
acc
acc
acc
acc
acc
acc
f754
dec
dec
dec
dec
dec
dec
dec
f755
ul
ul
ul
ul
fh
fh
fh
f756
ll
ll
ll
ll
ul
ul
ul
f757
thr
thr
thr
thr
ll
ll
ll
f758
fm
fm
fm
fm
thr
thr
thr
f759
-
pt
pt
pt
fm
fm
fm
f760
-
olm
olm
olm
pt
pt
pt
f761
-
sr1
sr1
f304
f201
f201
f216
f762
-
sr2
sr2
f308
f202
f202
f217
f763
-
sr3
sr3
f309
f203
f203
f218
f764
-
sr4
sr4
f328
f204
f204
f219
f765
-
sr5
sr5
f329
f207
f207
fpid
f766
-
sr6
sr6
f330
f216
f216
f359
f767
-
sr7
sr7
f331
f217
f217
f360
MODE
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......