E6581611
F-44
6
6.11 Operation
frequency
6.11.1 Starting frequency/ Stop frequency
f240
: Starting frequency
f243
: Stop frequency setting
Function
The frequency set with
is put out instantly when operation is started.
Use the
parameter when a delay in response of starting torque due to the
acceleration/deceleration time may affect the operation. Setting the starting frequency to a value from
0.5 to 3.0Hz is recommended. The occurrence of an overcurrent can be avoided by setting this
frequency below the rated slippage of the motor.
When starting: Frequency set with
f240
is output instantly.
When stopping: Output frequency turns to be 0Hz instantly with the frequency set with
f243
.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f240
Starting frequency
0.1-10.0 (Hz)
0.5
f243
Stop frequency setting
0.0: Same as
f240
0.1-30.0 (Hz)
0.0
Note: Set these parameters so that the starting frequency
f240
is higher than the stopping frequency
f243
.
If the
f240
–set frequency is lower than the
f243
–set frequency, the inverter doesn’t start when the
frequency command is
f243
–set frequency or less.
Starting frequency
Stopping frequency
Output frequency [Hz]
Time [s]
0
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......
Page 430: ......