E6581611
B-4
2
2.2.1
Standard connection diagram 1
This diagram shows a standard wiring of the main circuit.
MCCB
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
RES
S1
S2
CC
P24
OUT
NO
FM
CC
VIA
PP
+
-
Ry
VF-S15
*2
Reset
*3
M
*5
FLC
FLB
FLA
*4
*4
Noise
filter
MCCB(2P)
R/L1
S/L2/N
Power
supply
Single
phase
F
R
S3
RC
RY
+SU
+24
VIC
VIB
Meter
External potentiometer (1k-10k
)
7.5V-1mA
(or 0-10V/0(4)-20mA)
Frequency
meter
(ammeter)
Operation panel
RS485
connector
Protective function
activation output
Power circuit
Control
circuit
Motor
Voltage signal: 0-+10V
(or -10-+10V)
Current signal: 4(0)-20mA
Forward run command
Reverse run command
Preset-speed command 1
Preset-speed command 2
Common
Speed reach
signal output
Braking resistor
(
Option
)
Preset-speed command 3
Main circuit power supply
1ph-240V class: single-phase 200-240V
-50/60Hz
3ph-500V class: three-phase 380-500V
-50/60Hz
(or voltage signal between VIA and CC: 0-10V)
Standard connection diagram - SINK (Negative) (common:CC)
Low-speed
signal output
*1: The T/L3 terminal is not provided for
single-phase models.
Use the R/L1 and S/L2/N terminals as
input terminals.
*3: When using the OUT output terminal in
sink logic mode, short the NO and CC
terminals.
*5: To supply control power from an external
power supply for backing up the control
power supplied from the inverter, an optional
control power backup device (CPS002Z) is
required. In such a case, the backup device
is used at the same time with the internal
power supply of the inverter.
The optional control power backup unit can
be used with both 240V and 500V models.
*4: When VIA or VIB terminal is used as logic
input terminal, refer to section 7.2.1.
*6: Set the slide switch SW1 to sink side.
Refer to page B-11,12 for details.
Default setting is PLC side.
Control power
supply
CC
3ph-240V class: three-phase 200-240V
-50/60Hz
*2: The inverter is supplied with the PO
and the PA/+ terminals shorted by
means of a shorting bar.
Before installing the DC reactor (DCL),
remove the bar.
P0
PA/+
PC/-
PB
DC reactor (DCL)
*2
(option)
*6
SINK
SOURCE
SW1
PLC
VIB
SW2
PTC
S3
S4