11.6 Input
Terminal
Function
It can be assigned the function No. in the following table to parameter
f104
,
f108
,
f110
to
f118
,
f151
to
f156
,
a973
to
a976
.
Table of input terminal functions 1
Function
No.
Code Function
Action
Reference
0,1 -
No
function
Disabled
-
2
F
Forward run command
ON: Forward run, OFF: Deceleration stop
7.2.1
3
FN
Inversion of forward run command
Inversion of F
4
R
Reverse run command
ON: Reverse run, OFF: Deceleration stop
5
RN
Inversion of reverse run command
Inversion of R
6
ST
Standby
ON: Ready for operation
OFF: Coast stop (gate OFF)
3.1.1
5.9
7
STN
Inversion of standby
Inversion of ST
6.7.1
6.34.8
8
RES
Reset command 1 *2
ON: Acceptance of reset command, ON
¤
OFF: Trip reset
13.2
9
RESN
Inversion of reset command 1 *2
Inversion of RES
10
SS1
Preset-speed command 1
5.7
11
SS1N
Inversion of preset-speed command 1
7.2.1
12
SS2
Preset-speed command 2
13
SS2N
Inversion of preset-speed command 2
14
SS3
Preset-speed command 3
15
SS3N
Inversion of preset-speed command 3
16
SS4
Preset-speed command 4
5.7
17
SS4N
Inversion of preset-speed command 4
Selection of 15-speed SS1 to SS4 (SS1N to SS4N) (4 bits)
18
JOG
Jog run mode
ON: Jogging mode, OFF: Jog run canceled
6.14
19
JOGN
Inversion of jog run mode
Inversion of JOG
20
EXT
Emergency stop by external signal
ON:
trip stop, OFF: After stopped by
f603
,
e
trip
6.29.4
21
EXTN
Inversion of emergency stop by external signal
Inversion of EXT
22
DB
DC braking command
ON: DC braking, OFF: Brake canceled
6.12.1
23
DBN
Inversion of DC braking command
Inversion of DB
24
AD2
2nd acceleration/deceleration
ON: Acceleration/deceleration 2
OFF: Acceleration/deceleration 1
6.8.1
6.27.2
25
AD2N
Inversion of 2nd acceleration/deceleration
Inversion of AD2
26
AD3
3rd acceleration/deceleration
ON: Acceleration/deceleration 3
OFF: Acceleration/deceleration 1 or 2
27
AD3N
Inversion of 3rd acceleration/deceleration
Inversion of AD3
28
VF2
2nd V/F control mode switching
ON: 2nd V/F control mode
(V/F fixed,
,
,
,
(
thr
when
f632
=
2
or
3
))
OFF: 1st V/F control mode
(
setting,
,
,
,
)
6.8.1
29
VF2N
Inversion of 2nd V/F control mode switching
Inversion of VF2
32
OCS2
2nd stall prevention level
ON: Enabled at the value of
,
and
OFF: Enabled at the value of
,
and
6.8.1
6.29.2
33
OCS2N
Inversion of 2nd stall prevention level
Inversion of OCS2
36
PID
PID control prohibition
ON: PID control prohibited, OFF: PID control enabled
6.24
37
PIDN
Inversion of PID control prohibition
Inversion of PID
46
OH2
External thermal error input
ON:
oh2
trip stop, OFF: Disabled
7.2.1
47
OH2N
Inversion of external thermal error input
Inversion of OH2
48
SCLC
Forced local from communication
Enabled during communication
ON: Local (Setting of
,
)
OFF: Communication
6.2.1
6.38
49
SCLCN
Inversion of forced local from communication
Inversion of SCLC
50
HD
Operation hold (hold of 3-wire operation)
ON: F (forward run), R: (reverse run) held, 3-wire operation
OFF: Deceleration stop
7.2.1
51
HDN
Inversion of operation hold (hold of 3-wire
operation)
Inversion of HD
*2: These functions are cannot be assigned to Always active function selection 1 to 3 (
f104
,
f108
,
f110
).
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......
Page 430: ......