Q9 Plus Bypass ASD/Bypass Box Installation and Operation Manual
17
Read and understand all safety warnings before operating this equipment!
Motor Protection
Motor circuit protection is accomplished using circuit breakers that have adjustable trip thresholds. The
circuit breakers are set to the minimum current value of the circuit breaker at the factory and must be
adjusted for the motor being driven and the requirements of the application.
The motor protection hardware is comprised of a
Motor Circuit Protector
(MCP) at the three-phase
system input and an
Overload Circuit Protector
(OCP) connected to the motor (see
Overload settings are application-specific and should be set and/or adjusted by
ONLY
.
The
MCP
that is used on the
L1
,
L2
, and
L3
input power lines has a
Shunt Trip
feature that may be used
to further enhance the system protection function of the
Q9 Plus Bypass ASD/Q9 Plus Bypass Box
. The
Shunt Trip
feature may be connected such that the
L1
,
L2
, and
L3
MCP
may be opened by a state
change of the
LS
switch. The
LS
switch may be operated by an ancillary circuit or relay. If an ancillary
circuit is experiencing a condition that warrants a system shutdown (e.g., door is opened), the
L1
,
L2
, and
L3
MCP
will be opened by the completed
Shunt Trip
circuit. During normal operation, the
Shunt Trip
circuit is open.
Should the
Shunt Trip
circuit activate and terminate the three-phase input power, a manual reset is
required to resume normal system operation.