E6581611
K-32
11
Table of input terminal functions 3
Function
No.
Code Function
Action
Reference
100
RS
Run/Stop command
ON: Run command
OFF: Stop command
7.2.1
101
RSN
Inversion of run/Stop command
Inversion of RS
104
FCHG
Frequency setting mode forced switching
ON:
f207
(
f200
=
0
)
OFF:
fmod
6.2.1
105
FCHGN
Inversion of frequency setting mode forced
switching
Inversion of FCHG
106
FMTB
Frequency setting mode terminal block
ON: Terminal block (VIA) enabled
OFF: Setting of
107
FMTBN
Inversion of frequency setting mode terminal
block
Inversion of FMTB
108
CMTB
Command mode terminal block
ON: Terminal block enabled
OFF: Setting of
109
CMTBN
Inversion of command mode terminal block
Inversion of CMTB
110
PWE
Parameter editing permission
ON: Parameter editing permitted
OFF: Setting of
6.34.1
111
PWEN
Inversion of parameter editing permission
Inversion of PWE
120
FSTP1
Fast stop command 1
ON: Dynamic quick deceleration command
OFF: Forced deceleration canceled
(Note that operation is resumed when forced deceleration is canceled)
6.1.4
121
FSTP1N
Inversion of fast stop command 1
Inversion of FSTP1
122
FSTP2
Fast stop command 2
ON: Automatic deceleration
OFF: Forced deceleration canceled
(Note that operation is resumed when forced deceleration is canceled)
123
FSTP2N
Inversion of fast stop command 2
Inversion of FSTP2
134
TVS
Traverse permission signal
ON: Permission signal of traverse
operation
OFF: Normal operation
6.40
135
TVSN
Inversion of traverse permission signal
Inversion of TVS
136
RSC
Low voltage operation signal
ON: Low voltage operation
OFF: Low voltage operation canceled
6.17
137
RSCN
Inversion of low voltage operation signal
Inversion of RSC
140 SLOWF Forward
deceleration
ON: Forward operation with
f383
frequency
OFF: Normal operation
6.22.2
141
SLOWFN
Inversion of forward deceleration
Inversion of SLOWF
142 STOPF Forward
stop ON:
Forward
stop, OFF: Normal operation
143 STOPFN
Inversion
of
forward
stop
Inversion of STOPF
144 SLOWR Reverse
deceleration
ON: Reverse operation with
f383
frequency
OFF: Normal operation
145
SLOWRN
Inversion of reverse deceleration
Inversion of SLOWR
146 STOPR Reverse
stop ON:
Reverse
stop, OFF: Normal operation
147
STOPRN
Inversion of reverse
stop
Inversion of STOPR
148 to 151
Factory specific coefficient
-
*1
152 MOT2 No.2
motor
switching
(
AD2
+
VF2
+
OCS2
)
ON: No.2 motor
(
=0,
,
,
,
(
thr
when
f632
=
2
or
3
),
,
,
,
)
OFF: No.1 motor (Set value of
,
,
,
,
,
,
,
,
)
6.8.1
153
MOT2N
Inversion of No.2 motor switching
(
AD2
+
VF2
+
OCS2
)
Inversion of MOT2
158
RES2
Reset command 2 *2
ON: Trip reset
13.2
159
RES2N
Inversion of reset command 2 *2
Inversion of RES2
200
PWP
Parameter editing prohibition
ON: Parameter editing prohibited
OFF: Setting of
6.34.1
201
PWPN
Inversion of parameter editing prohibition
Inversion of PWP
202
PRWP
Parameter reading prohibition
ON: Parameter reading / editing prohibited
OFF: Setting of
203
PRWPN
Inversion of parameter reading prohibition
Inversion of PRWP
*1: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
*2: These functions are cannot be assigned to Always active function selection 1 to 3 (
f104
,
f108
,
f110
).
Note 1: Function No. that are not described in the table above are assigned "No function".