E6581611
F-59
6
In case of
aul
=
2
(Variable torque characteristic (120%-60s)) setting.
PWM carrier frequency
VFS15-
Ambient
temperature
2.0k
~
4.0kHz
4004 PL-W
40
°
C or less
2.1 A
4007 PL-W
40
°
C or less
3.0 A
4015 PL-W
40
°
C or less
5.4A
4022 PL-W
40
°
C or less
6.9 A
4037 PL-W
40
°
C or less
11.1 A
4055 PL-W
40
°
C or less
17.0A
4075
PL-W
40
°
C or less
23.0 A
4110
PL-W
40
°
C or less
31.0A
4150 PL-W
40
°
C or less
38.0A
* In case of
=
2
setting, be sure to install the input AC reactor (ACL) between power supply and inverter
and use at ambient temperature 40°C or less. Set
f300
to 4.0 kHz or less.
* If
parameter
f316
=
0
or
2
and current is increased to main module overheat level (
ol3
) or to overheat
level (
oh
), the
l
alarm or
h
alarm occurs. If the cumulative amount of overload is increased further,
ol3
trip or
oh
trip occurs.
In this case, to avoid such trips, reduce the stall prevention level (
f601
) properly.
* If
parameter
f316
=
2
or
3
, setting parameter
f300
to 4.0kHz or less is recommended. Output voltage
may be reduced.
* PWM carrier frequency is increased at high output frequency area for stable operation, even if
f300
is set
to low PWM carrier frequency.
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......
Page 430: ......