E6581611
B-9
2
Terminal
symbol
Input /
output
Function
Electrical
specifications
Inverter internal circuits
FM Output
Multifunction programmable analog
output. Default setting: output frequency.
The function can be changed to ammeter,
0-10Vdc voltage or 0-20mAdc (4-20mA)
current output by parameter
setting.
Resolution Max. 1/1000.
1mAdc full-scale
ammeter or
QS60T(option)
0-20mA (4-20mA)
DC ammeter
Permissible load
resistance:
600
Ω
or less
0-10V DC volt
meter
Permissible load
resistance:
1k
Ω
or more
Output
24Vdc power output
24Vdc-100mA
Note 2)
P24
Input
This terminal can be used as a common
terminal when an external power supply
is used by changing SW1 to PLC side.
-
+24
Output
24Vdc power output
24Vdc-100mA
Note 2)
+SU Input
DC power input terminal for operating the
control circuit. Connect a control power
backup device (option or 24Vdc power
supply) bSU and CC.
Voltage: 24Vdc
±
10%
Current: 1A or
more
+24V
Current
limiter
+24
P24
EXT
SW1
+24V
+SU
1
+24V
68
121
Current
+
–
Voltage
+
–
FM
+24V