E6581611
E-16
5
5.7
Preset-speed operation (speeds in 15 steps)
sr0
to
sr7
: Preset-speed frequency 0 to 7
f287
to
f294
: Preset-speed frequency 8 to15
f724
: Operation frequency setting target by setting dial
Function
A maximum of 15 speed steps can be selected just by switching an external logic signal. Multi-speed
frequencies can be programmed anywhere from the lower limit frequency
to the upper limit frequency
.
[Setting method]
1) Run/stop
The starting and stopping control is done from the terminal block.
Title Function
Adjustment
range
Setting
Command
mode
selection
0: Terminal block
1: Panel keypad (including extension panel)
2: RS485 communication
3: CANopen communication
4: Communication option
0
2)
Preset-speed frequency setting
a) Set the speed (frequency) of the number of steps necessary.
[Parameter setting]
Preset-speed 0
Title
Function
Adjustment range
Default setting
sr0
Preset-speed frequency 0
-
(Hz) 0.0
fmod
Frequency setting mode selection 1
0-13
14:
sr0
0
Frequency command set with
sr0
is valid when
fmod
=
14
(
sr0
).
(
sr0
is valid even when the command mode selection is not
cmod
=
0
.)
Setting from speed 1 to speed 15
Title
Function
Adjustment range
Default setting
-
Preset-speed frequency 1-7
-
(Hz) 0.0
Preset-speed frequency 8-15
(Hz)
0.0
b) Speed (frequency) can be changed during operation.
Title Function
Adjustment
range
Setting
Operation frequency setting target
by setting dial
0: Panel frequency (
fc
)
1: Panel frequency (
fc
)
+ Preset speed frequency
1
When
f724
=
1
, speed (frequency) can be changed with the setting dial during operation. Set value of the
Preset-speed frequency will change by pressing the center.