E6581611
K-5
11
11.3 Extended
parameters
Input/output
parameters
1
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0100 Low-speed
signal
output frequency
Hz 0.1/0.01
0.0-
0.0
6.5.1
0101
Speed reach
setting frequency
Hz 0.1/0.01
0.0-
0.0
6.5.3
0102
Speed reach
detection band
Hz 0.1/0.01
0.0-
2.5
6.5.2
6.5.3
0104 Always
active
function selection 1
-
-
0-153 *6
0 (No
function)
6.7.1
0105 Priority
selection
(Both F and R are
ON)
-
-
0: Reverse
1: Deceleration Stop
1
6.6.1
0107 Analog
input
terminal selection
(VIB)
-
-
0: 0-+10V
1: -10-+10V
0
6.6.2
6.10.2
7.3
0108 Always
active
function selection 2
-
-
0-153 *6
0 (No
function)
6.7.1
0: VIA - analog input
VIB
-
analog input
1: VIA - analog input
VIB
-
contact input
2: -
3: VIA
-
contact input (Sink)
VIB
-
contact input
0109 Analog/logic
input
selection
(VIA/VIB)
- -
4: VIA
-
contact input (Source)
VIB
-
contact input
0
6.6.3
6.7.2
6.10.2
7.2.1
7.3
0110 Always
active
function selection 3
-
-
0-153 *6
6
(ST)
6.7.1
0111 Input
terminal
selection 1A (F)
- -
2
(F)
0112 Input
terminal
selection 2A (R)
- -
4
(R)
0113 Input
terminal
selection 3A (RES)
- -
8
(RES)
0114 Input
terminal
selection 4A (S1)
- -
10
(SS1)
0115 Input
terminal
selection 5 (S2)
- -
12
(SS2)
6.7.2
7.2.1
0116 Input
terminal
selection 6 (S3)
- -
14
(SS3)
0117 Input
terminal
selection 7 (VIB)
- -
0-203 *6
16
(SS4)
0118 Input
terminal
selection 8 (VIA)
-
-
8-55 *6
24
(AD2)
*6: Refer to section 11.6 for details about input terminal function.