E6581611
B-5
2
2.2.2
Standard connection diagram 2
MCCB
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
RES
FM
CC
VIA
PP
+
-
VF-S15
*2
M
*5
FLC
FLB
FLA
*4
*4
MCCB(2P)
R/L1
S/L2/N
S3
RC
RY
CC
+SU
Control power
supply
VIC
VIB
P24
OUT
NO
CC
*3
Ry
F
R
S1
S2
Reset
Power circuit
Control
circuit
Motor
Forward run command
Reverse run command
Preset-speed command 1
Preset-speed command 2
Preset-speed command 3
Operation panel
RS485
connector
Voltage signal: 0-+10V
(or -10-+10V)
Current signal: 4(0)-20mA
Speed reach
signal output
Protective function
activation output
Main circuit power supply
1ph-240V class: single-phase 200-240V
-50/60Hz
3ph-500V class: three-phase 380-500V
-50/60Hz
Power
supply
Single
phase
Meter
External potentiometer (1k-10k
)
7.5V-1mA
(or 0-10V/4-20mA)
Frequency
meter
(ammeter)
(or voltage signal between VIA and CC: 0-10V)
Standard connection diagram - SOURCE (Positive) (common:P24)
Noise
filter
Low-speed
signal output
+24
Common
3ph-240V class: three-phase 200-240V
-50/60Hz
Braking resistor
(
Option
)
P0
PA/+
PC/-
PB
DC reactor (DCL)
*2 (option)
VIB
SW2
PTC
S3
S4
*6
SINK
SOURCE
SW1
PLC
*1: The T/L3 terminal is not provided for
single-phase models.
Use the R/L1 and S/L2/N terminals as
input terminals.
*3: When using the NO output terminal in
source logic mode, short the P24 and
OUT terminals.
*5: To supply control power from an external
power supply for backing up the control
power supplied from the inverter, an optional
control power backup device (CPS002Z) is
required. In such a case, the backup device
is used at the same time with the internal
power supply of the inverter.
The optional control power backup unit can
be used with both 240V and 500V models.
*4: When VIA or VIB terminal is used as logic
input terminal, refer to section 7.2.1.
*6: Set the slide switch SW1 to source side.
Refer to page B-11,12 for details.
Default setting is PLC side.
*2: The inverter is supplied with the PO
and the PA/+ terminals shorted by
means of a shorting bar.
Before installing the DC reactor (DCL),
remove the bar.
Summary of Contents for Q9 Plus ASD