E6581611
F-125
6
Title
Function
Adjustment range
Default setting
f734
Panel emergency stop operation
prohibition
0: Permitted, 1: Prohibited
0
f735
Panel reset operation prohibition
0: Permitted, 1: Prohibited
0
f736
cmod
/
fmod
change prohibition
during operation
0: Permitted, 1: Prohibited
1
All key operation prohibition
0: Permitted, 1: Prohibited
0
f738
Password setting (
f700
)
0: Password unset
1-9998
9999: Password set
0
f739
Password verification
0: Password unset
1-9998
9999: Password set
0
,
Parameters can be edited regardless of the setting of
f700
by assigning the parameter editing
permission (function number 110, 111) to an input terminal.
Note1:
f700
=
2
and
4
will be available after reset operation.
When protection using a password is necessary, set and remove with the following method.
■
Password setup method
Preparation: Parameters other than
f700
,
f738
, and
f739
cannot be changed when
f700
is set
to
1
to
4
.
(1) When
f738
or
f739
is read out and the value is
0
, a password hasn’t been set.
You can set a password.
(2) When
f738
or
f739
is read out and the value is
9999
, a password has already been set.
(3) You can set a password If it hasn’t been set. Select and register a number from
1
to
9998
for
f738
.
The number is the password. Do not forget your password as it is required to release the lock.
(4) The settings for parameter
f700
cannot be changed.
Note2: The lock cannot be released If you forget the password. Do not forget this password as we cannot
retrieve it.
Note3: Password cannot be set when parameter
f700
=
0
.
Set the password after parameter
f700
=
1
to
4
.
Note4: Password can be read out to parameter writer (optional device) only for 5 minutes after setting
. Please note that password will not be able to read out due to password protection after 5
minutes have elapsed or when the power is off.
■
Password examination method
(1) When
f738
or
f739
are read out and the value is
9999
, a password has already been set.
Password has to be removed in order to change parameters.
(2) Enter a the number (
1
to
9998
) registered to
f739
when the password was set for
f738
.
(3) If the password matches,
pass
blinks on the display and the password is removed.
(4) If the password is incorrect,
fail
blinks on the display and
f739
is displayed again.
(5) When the password is removed, the setting for parameter
f700
can be changed.
(6) By setting parameter
f700
=
0
, the all parameter settings can be changed.
Note5: Entry of
setting is possible up to 3 times. Please note it is impossible to set, if you enter the
wrong number for 3 times. Number of times is reset after power is off.