6.19 Trip-less
intensification
6.19.1 Auto-restart (Restart of coasting motor)
f301
: Auto-restart control selection
⇒
Refer to section 5.9 for details.
6.19.2 Regenerative power ride-through control/Deceleration stop
during power failure/Synchronized acceleration/deceleration
f302
: Regenerative power ride-through control (Deceleration stop)
f317
: Synchronized deceleration time
f318
: Synchronized acceleration time
[Parameter setting]
Title
Function
Adjustment range
Default setting
f302
Regenerative power ride-through
control (Deceleration stop)
0: Disabled
1: Regenerative power ride-through control
2: Deceleration stop during power failure
3: Synchronized acceleration / deceleration
(signal)
4: Synchronized acceleration / deceleration
( power failure)
0
f317
Synchronized deceleration time
(time elapsed between start of
deceleration to stop)
0.0-3600 (360.0) (s)
2.0
f318
Synchronized acceleration time
0.0-3600 (360.0) (s)
2.0
• Function
1) Regenerative power ride-through control: When momentary power failure occurs during operation, this
function makes operation continue using the regeneration
energy from a motor.
2) Deceleration stop during power failure:
When momentary power failure occurs during operation, this
function stops the motor quickly and compulsorily using the
regeneration energy from the motor.
(Deceleration time varies according to control.) When operation
is stopped, the message “
” blinks on the operation panel.
After the forced stop, the inverter remains static until you put off
the operation command momentarily.
3) Synchronized acceleration/deceleration: When the inverter is used with textile machines, this function
decelerate the motors synchronously to stop in the event of a
momentary power failure and accelerate them to reach the
targeted frequency commands synchronously at the recovery
from the power failure in order to prevent thread breakage.
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......
Page 430: ......