E6581611
A-33
1
Installing more than one unit in a cabinet
When two or more inverters are installed in one cabinet, pay attention to the followings.
Inverters may be installed side by side with each other with no space left between them.
When installing inverters side by side, remove the protective label on the top of the inverter.
When using the inverter in locations with temperatures above 40°C, use the inverter with the output
current reduced.
Ensure a space of at least 20 centimeters on the top and bottom of the inverters.
Install an air deflecting plate so that the heat rising up from the inverter on the bottom does not affect the
inverter on the top.
Ventilation fan
Inverter
Air deflecting plate
Inverter