6.33 Adjustment
parameters
6.33.1 Inputting integral input power pulse
:
Integral input power pulse output unit
:
Integral input power pulse output width
•
Function
Pulse signal can be output each time integral input power reaches integral power unit that is set by
f667
.
Pulse output width is set by
f668
.
[Parameter setting]
Title
Function
Adjustment range
Default setting
Integral input power pulse output unit
0: 0.1kWh
1: 1kWh
2: 10kWh
3: 100kWh
1
Integral input power pulse output width
0.1-1.0 (s)
0.1
Setting example) When integral input power pulse is output from output terminal
Title Function Adjustment
range
Setting
Output terminal selection 2A
0 - 255
180:
IPU (Integral input
power pulse output signal)
There is no reverse signal.
6.33.2 Pulse train output for meters
f669
: Logic output/pulse train output selection (OUT)
f676
: Pulse train output function selection (OUT)
f677
: Maximum numbers of pulse train output
f678
: Pulse train output filter
•
Function
Pulse trains can be sent out through the OUT output terminals.
Set a pulse output mode and the number of pulses.
Ex.: When operations frequencies (0 to 60Hz) are put out by means of 0 to 600 pulses
fh
=60.0,
f669
=1,
f676
=0,
f677
=0.60