E6581611
M-3
13
(Continued)
Error code
Failure code
Problem
Possible causes
Remedies
*
0048 Over-torque
/
Overcurrent fault
Power running torque or output current
reached
f593
or more and maintain in
f595
during power running.
Enable
.
Reduce the load.
Check system error.
*
0049 Small-torque
/
Small
-current fault
Power running torque or output current
decreased
f593
or less and maintain
in
f595
during power running.
Enable
.
Check system error.
The cooling fan does not rotate.
The fan requires replacement if it does
not rotate during operation.
The ambient temperature is too high.
Restart the operation by resetting the
inverter after it has cooled down enough.
The vent is blocked up.
Secure sufficient space around the inverter.
0010 Overheat
A heat generating device is installed close
to the inverter.
Do not place any heat generating device
near the inverter.
002E
Thermal fault stop
command from
external device
A thermal trip command (input terminal
function:
or
) is issued by an
external control device.
The motor is overheated, so check
whether the current flowing into the motor
exceeds the rated current.
0011 Emergency
stop
During automatic operation or remote
operation, a stop command is entered
from the operation panel or a remote
input device.
Reset the inverter.
If the emergency stop signal is input,
reset after releasing this signal.
0012 EEPROM fault 1
A data writing error occurs.
Turn off the inverter, then turn it again. If it
does not recover from the error, contact
your Toshiba distributor.
0013 EEPROM fault 2
Power supply is cut off during
operation and data writing is aborted.
The error occurred when various data
was written.
Turn the power off temporarily and turn it
back on, and then try
operation
again.
Write the data again. Contact your
Toshiba distributor when it happening
frequently.
0014 EEPROM fault 3
A data reading error occurred.
Turn off the inverter, then turn it again. If it
does not recover from the error, contact
your Toshiba distributor.
0015
Main unit RAM fault
The control RAM is defective.
Contact your Toshiba distributor.
0016
Main unit ROM fault
The control ROM is defective.
Contact your Toshiba distributor.
0017 CPU
fault
1
The control CPU is defective.
Contact your Toshiba distributor.
0018 Communication
error
The communication was broken off.
Check the remote control device, cables,
etc.
001A Current
detector
fault
The current detector is defective.
Contact your Toshiba distributor.
001B
Optional unit fault 1
An optional unit has failed.
(such as a communication option)
Check the connection of optional unit.
001C Remote
keypad
disconnection fault
After run signal is activated by RUN key
of the remote keypad, disconnection is
occurred in 10 seconds or more.
In case the remote keypad is
disconnected, press STOP key before.
This fault is disabled by
f731
=
1
setting.
*
001D Low-current
operation
fault
The output current decreased to a low-
current detection level during operation.
Enable
(low-current detection).
Check the suitable detection level for the
system (
,
,
).
Contact your Toshiba distributor if the
setting is correct.
*
001E Undervoltage
fault
(main circuit)
The input voltage (in the main circuit) is
too low.
Check the input voltage.
Enable
(undervoltage trip
selection).
To take measures to momentary power
failure, set
=
, Regenerative
power ride-through control
f302
and
Auto-restart control selection
f301
.
* This marking trips can be selected valid or invalid by parameters.
(Continued overleaf)
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......
Page 430: ......