E6581611
F-128
6
In this case, the output frequency displayed in standard monitor mode changes by 0.1 Hz, as usual.
■
When
f707
is not 0.00, and
f708
is not 0
The value displayed on the panel also can also be changed in steps.
Output frequency displayed in standard monitor mode = Internal output frequency
×
[Parameter setting]
Title
Function
Adjustment range
Default setting
f707
Free step 1 (1-step rotation of setting
dial)
0.00: Automatic
0.01-
fh
(Hz)
0.00
f708
Free step 2 (panel display)
0: Automatic
1-255
0
■
Operation example 1
f707
= 0.00 (disabled)
By rotating the setting dial 1 step, the panel frequency command value changes only 0.1 Hz.
When
f707
= 10.00 (Hz) is set
Rotating the setting dial 1 step changes the panel frequency command value in 10.00 Hz increments, from
0.00 up to 60.00 (Hz).
■
Operation example 2
When
f707
=1.00 (Hz), and
f708
=1:
By rotating the setting dial 1 step, the frequency setting
fc
changes in steps of 1Hz: 0
→
1
→
2
→
...
→
60
(Hz) and also the value displayed on the operation panel changes in steps of 1. Use these settings to hide
decimal fractions and also the value displayed on the operation panel changes in steps of 1. Use these
settings to hide decimal fractions.
6.34.5 Select the initial display of the panel
f710
: Initial panel display selection
f720
: Initial extension panel display selection
•
Function
This parameter specifies display format of the standard monitor mode when power is ON. Different
contents can be displayed on the operation panel of main unit and the extension panel (option).
■
Changing the display format while power is ON
When the power is ON, the standard monitor mode displays the output frequency (default setting) such as
"
0.0
" or "
off
". This format can be changed to any other monitor display format by setting
f710
.
However, the initial letter including
t
or
c
will not be displayed. When the power is ON, set the display of the
extension panel at
f720
.
,
Different contents can be displayed on the operation panel of main unit and the extension panel (option).
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......
Page 430: ......