E6581611
F-94
6
6.26.3 Power running stall continuous trip detection time
f452
: Power running stall continuous trip detection time
• Function
A function for preventing lifting gear from failing accidentally. If the stall prevention function is activated in
succession, the inverter judges that the motor has stalled and trips.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f452
Power running stall continuous trip detection time
0.00-10.00 (s)
0.00
f441
Power running torque limit 1 level
0-249%,
250:Disabled
250
f601
Stall prevention level 1
10-199
,
200 (disabled)
150
1) In case of overcurrent stall
ot2
trip is occurred if the output current reached the stall prevention level (
f601
) or more, and this situation
maintain in
f452
during power running.
Time [s]
Output frequency [Hz]
Time [s]
Output current [%]
less than
“
2
” trip