E6581611
K-34
11
11.7 Output
Terminal
Function
It can be assigned the function No. in the following table to parameter
f130
to
f138
,
f157
,
f158
.
Table of output terminal functions 1
Function
No.
Code Function
Action
Reference
0
LL
Frequency lower limit
ON: Output frequency is more than
OFF: Output frequency is
or less
5.4
1
LLN
Inversion of frequency lower limit
Inversion of LL
2
UL
Frequency upper limit
ON: Output frequency is
or more
OFF: Output frequency is less than
3
ULN
Inversion of frequency upper limit
Inversion of UL
4
LOW
Low-speed detection signal
ON: Output frequency is
or more
OFF: Output frequency is less than
6.5.1
7.2.2
5
LOWN
Inversion of low-speed detection signal
Inversion of LOW
6
RCH
Output frequency attainment signal
(acceleration/deceleration completed)
ON: Output frequency is within command frequency
OFF: Output frequency is more than command frequency
6.5.2
7.2.2
7
RCHN
Inversion of output frequency attainment
signal
(inversion of acceleration/deceleration
completed)
Inversion of RCH
8
RCHF
Set frequency attainment signal
ON: Output frequency is within
±
OFF: Output frequency is more than
±
6.5.3
9
RCHFN
Inversion of set frequency attainment signal
Inversion of RCHF
10
FL
Fault signal (trip output)
ON: Inverter tripped
OFF: Inverter not tripped
7.2.2
11
FLN
Inversion of fault signal (inversion of trip
output)
Inversion of FL
14
POC
Over-current detection pre-alarm
ON: Output current is
or more
OFF: Output current is less than
6.29.2
15
POCN
Inversion of over-current detection pre-alarm
Inversion of POC
16
POL
Overload detection pre-alarm
ON:
(%) or more of calculated value of overload
protection level
OFF: Less than
(%) of calculated value of overload
protection level
5.6
17
POLN
Inversion of overload detection pre-alarm
Inversion of POL
20
POH
Overheat detection pre-alarm
ON: Approx. 95
C or more of IGBT element
OFF: Less than approx. 95
C of IGBT element (90
C or less
after detection is turned on)
7.2.2
21
POHN
Inversion of overheat detection pre-alarm
Inversion of POH
22
POP
Overvoltage detection pre-alarm
ON: Overvoltage limit in operation
OFF: Overvoltage detection canceled
6.19.5
23
POPN
Inversion of overvoltage detection pre-alarm
Inversion of POP
24
MOFF
Power circuit undervoltage detection
ON: Power circuit undervoltage (MOFF) detected
OFF: Undervoltage detection canceled
6.29.13
25
MOFFN
Inversion of power circuit undervoltage
detection
Inversion of MOFF
26
UC
Small current detection
ON: After output current comes to
or less, value of
less than
+
for
set time
OFF: Output current is more than
(
+
or more after detection turns on)
6.29.7
27
UCN
Inversion of small current detection
Inversion of UC
28
OT
Over-torque detection
ON: After torque comes to
or more, value of more
than
-
for
set time
OFF: Torque is less than
(
-
or less after detection turns on)
6.29.10
29
OTN
Inversion of over-torque detection
Inversion of OT