E6581611
L-1
12
12. Specifications
12.1 Models and their standard specifications
Standard specifications
Item Specification
Input voltage
3-phase 240V
Applicable
motor
(kW)
0.4 0.75 1.5 2.2 4.0 5.5 7.5 11 15
Type VFS15
Form 2004PM-W
2007PM-W 2015PM-W 2022PM-W 2037PM-W 2055PM-W 2075PM-W 2110PM-W
2150PM-W
Capacity (kVA) Note 1)
1.3
1.8
3.0
4.2
6.7
10.5
12.6
20.6
25.1
Rated output/current
(A) Note 2)
3.3
(3.3)
4.8
(4.4)
8.0
(7.9)
11.0
(10.0)
17.5
(16.4)
27.5
(25.0)
33.0
(33.0)
54.0
(49.0)
66.0
(60.0)
Output voltage Note 3)
3-phase 200V to 240V
Rat
ing
Overload current rating
150
%
-60 seconds, 200%-0.5 second
Voltage-frequency
3-phase 200V to 240V - 50/60Hz
Allowable fluctuation
Voltage 170V to 264V Note 4), frequency ±5%
Po
w
er
s
up
pl
y
Required Power supply
capacity (kVA) Note 5)
1.4 2.5 4.3 5.7 9.2 13.8
17.8 24.3 31.6
Protection degree (IEC60529)
IP20
Cooling method
Self-cooling
Forced air-cooled
Color
RAL7016
Built-in filter
Basic filter
Item
Specification
Input voltage
1-phase 240V
3-phase 500V
Applicable motor (kW)
0.2
0.4
0.75
1.5
2.2
0.4
0.75
1.5
2.2
4.0
5.5
7.5
11
15
Type VFS15S
VFS15
Form
2002PL
-W
2004PL
-W
2007PL
-W
2015PL
-W
2022PL
-W
4004PL
-W
4007PL
-W
4015PL
-W
4022PL
-W
4037PL
-W
4055PL
-W
4075PL
-W
4110PL
-W
4150PL
-W
Capacity (kVA) Note 1)
0.6
1.3
1.8
3.0
4.2
1.1
1.8
3.1
4.2
7.2
10.9
13.0
21.1
25.1
Rated output current
(A) Note 2)
1.5
(1.5)
3.3
(3.3)
4.8
(4.4)
8.0
(7.9)
11.0
(10.0)
1.5
(1.5)
2.3
(2.1)
4.1
(3.7)
5.5
(5.0)
9.5
(8.6)
14.3
(13.0)
17.0
(17.0)
27.7
(25.0)
33.0
(30.0)
Rated output voltage Note 3)
3-phase 200V to 240V
3-phase 380V to 500V
Rat
ing
Overload current rating
150
%
-60 seconds, 200%-0.5 second
150
%
-60 seconds, 200% -0.5 second
Voltage-current
1-phase 200V to 240V – 50/60Hz
3-phase 380V to 500V - 50/60Hz
Allowable fluctuation
Voltage 170V to 264V Note 4),
frequency±5
%
Voltage 323V to 550V Note 4), frequency ±5%
Po
w
er
s
up
pl
y
Required Power supply
capacity (kVA) Note 5)
0.8 1.4 2.3
4.0
5.4 1.6
2.7
4.7
6.4
10.0
15.2
19.5 26.9
34.9
Protection degree (IEC60529)
IP20
IP20
Cooling method
Self-cooling
Forced air-
cooled
Forced air-cooled
Color RAL7016
RAL7016
Built-in filter
EMC filter
EMC filter
Note 1. Capacity is calculated at 220V for the 240V models, at 440V for the 500V models.
Note 2. Indicates rated output current setting when the PWM carrier frequency (parameter
f300
) is 4kHz or less. When
exceeding 4kHz, the rated output current setting is indicated in the parentheses. It needs to be further reduced for
PWM carrier frequencies above 12 kHz.
The rated output current is reduced even further for 500V models with a supply voltage of 480V or more.
The default setting of the PWM carrier frequency is 12kHz.
Note 3. Maximum output voltage is the same as the input voltage.
Note 4. At 180V-264V for the 240V models, at 342V-550V for the 500V models when the inverter is used continuously (load of
100%).
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......