E6581611
F-80
6
1) External
connection
2) Selecting process value and feedback value
Process value (frequency) and feedback value can be combined as follows for the PID control.
(1) Process value
(2) Feedback value
PID control reference signal selection
f389
PID control feedback signal selection
0:
fmod
/
f207
selected
1: Terminal VIA
2: Terminal VIB
3:
fpid
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4 to 6: -
Note 1: When setting
f389
, do not select the same signal used for feedback input.
Note 2: When
3
is selected at
f389
, the amount of processing will be the value set at
fpid
.
Value of
fpid
can be set or changed during operation with the use of setting dial, and then saved in
fpid
. Please note that this value is not for
fc
setting (panel operation frequency).
Note 3: Signal is put out when the amount of feedback matches to the amount of processing. Assign function
number 144 or 145 to an output terminal.
M
P
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
VIA
CC
Pressure
transmitter
(1) Process
value
DC: 0 to 10V
(2)Feedback signals DC : 4~20mA
CC
VIC