E6581611
K-8
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0209 Analog
input
filter
ms 1/1 2-1000
64 6.10.2
0210
VIB input point 1
setting
% 1/1
-100-+100
0 7.3
0211
VIB input point 1
frequency
Hz 0.1/0.01
0.0-500.0
0.0
0212
VIB input point 2
setting
% 1/1
-100-+100
100
0213
VIB input point 2
frequency
Hz 0.1/0.01
0.0-500.0
*1
0214
VIB input point 1
rate
% 1/0.01
-250-+250
0
6.31
6.32
0215
VIB input point 2
rate
% 1/0.01
-250-+250
100
0216
VIC input point 1
setting
% 1/1
0-100
20
6.10.2
7.3
0217
VIC input point 1
frequency
Hz 0.1/0.01
0.0-500.0
0.0
0218
VIC input point 2
setting
% 1/1
0-100
100
0219
VIC input point 2
frequency
Hz 0.1/0.01
0.0-500.0
*1
0220
VIC input point 1
rate
% 1/0.01
0-250
0
6.31
0221
VIC input point 2
rate
% 1/0.01
0-250
100
0239 Factory
specific
coefficient 2A
- -
-
- *
3
0240 Starting
frequency
Hz 0.1/0.01
0.1-10.0
0.5 6.11.1
0241 Operation
starting
frequency
Hz 0.1/0.01
0.0-
0.0
6.11.2
0242 Operation
starting
frequency
hysteresis
Hz 0.1/0.01
0.0-
0.0
0243 Stop
frequency
setting
Hz
0.1/0.01
0.0: Same as
0.1-30.0
0.0
6.11.1
0249 PWM
carrier
frequency during
DC braking
kHz
0.1/0.1 2.0-16.0
4.0
6.12.1
0250 DC
braking
starting frequency
Hz 0.1/0.01
0.0-
0.0
0251 DC
braking
current
%(A)
1/1 0-100
50
0252
DC braking time
s
0.1/0.1
0.0-25.5
1.0
0254
Motor shaft fixing
control
- -
0:
Disabled
1: Enabled (after DC braking)
0
6.12.2
0256
Time limit for
lower-limit
frequency
operation
s 0.1/0.1
0:
Disabled
0.1-600.0
0.0 6.13
0257 Factory
specific
coefficient 2B
- -
-
- *
3
0258 Factory
specific
coefficient 2C
- -
-
- *
3
0259 Lower
limit
frequency reach
time limit at start-
up
s 0.1/0.1
0.0:
Disabled
0.1-600.0
0.0 6.13
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.