E6581611
F-38
6
For details about analog signal setting, refer to section 7.3.
1) 0-10Vdc voltage input adjustment (VIA, VIB terminals)
Adjust the frequency command for
the voltage input by setting the two
points.
/
100 (%)
10V voltage signal
/
0 ( Hz)
/
0 (%)
0
/
50/60 (Hz)
Frequency commnd
2) 4-20mAdc current input adjustment (VIC terminal)
Adju st t he fr eq ue nc y c om m and f or th e
cu rr en t in pu t b y s ettin g the t wo po ints.
S et
to
in cas e o f a cu rr e nt
in pu t o f 0 to 2 0 m A .
10 0 ( %)
2 0mA cu r re n t sig n al
0 ( Hz)
2 0 (% )
4m A
50 /60 ( Hz)
Frequency commnd
3) -10-+10 Vdc voltage input adjustment (VIB terminal)
Adjust the frequency
command for the voltage
input by setting the two
points.
50/60 (Hz)
100(%)
10V voltage signal
-100(%)
-10V
f213
50/60 (Hz)
Forward run
Reverse run
0(Hz)
0(%)