f205
: VIA input point 1 rate
f206
: VIA input point 2 rate
f214
: VIB input point 1 rate
f215
: VIB input point 2 rate
f220
: VIC input point 1 rate
f221
: VIC input point 2 rate
f660
: Override addition input selection
f661
: Override multiplication input selection
f729
: Operation panel override multiplication gain
• Function
These parameters are used to adjust reference frequencies by means of external input.
[Parameter setting]
Title
Function
Adjustment range
Default setting
VIA input point 1 rate
0-250 (%)
0
VIA input point 2 rate
0-250 (%)
100
VIB input point 1 rate
-250-+250 (%)
0
VIB input point 2 rate
-250-+250 (%)
100
VIC input point 1 rate
0-250 (%)
0
VIC input point 2 rate
0-250 (%)
100
f660
Override addition input selection
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4:
fc
0
f661
Override multiplication input
selection
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4:
f729
0
Operation panel override
multiplication gain
-100-+100 (%)
0