Example of 4-20mA output adjustment (Refer to section 6.17.2 for details)
=
1
,
=
0
=
1
,
=
20
Output
currrent
Output
currrent
Internal calculated value
Internal calculated value
0
20
(mA)
0
100%
4
20
(mA)
0
100%
f692
fm
fm
Note 1) When using the FM terminal for current output, be sure that the external load resistance is less than 600
Ω
.
Use over 1k
Ω
external load resistance for voltage output.
Note 2)
=
is the motor drive frequency.
Adjusting the meter in inverter stop state
Adjustment of the meter for output current (
=
1
)
Adjustment of the meter for output current can be done in inverter stop state.
When setting
to
for fixed output 1 (output current 100% equivalent), a signal assuming that
inverter rated current (output current 100% equivalent) passes will be output from the FM terminal.
Adjust the meter with the
(Meter adjustment) parameter in this state.
Similarly, if you set
to
for fixed output 2 (output current 50% equivalent), a signal assuming
that 50% of inverter rated current (output current 50% equivalent) passes will be output from the FM
terminal.
After meter adjustment is ended, set
to
(output current).
Other adjustments (
=
,
to
7
,
9
to
,
,
,
,
to
)
=
: When fixed output 3 (other than the output current) is set, a signal of the value for other
monitors is fixed at the following values and output through the FM terminal.
100% standard value for each item is the following:
=
0
,
2
,
12
,
: Maximum frequency (
h
)
=
3
,
4
: 1.5 times of rated voltage
=
7
: 2.5 times of rated torque
=
9
to
11
: Rated load factor
=
13
,
,
,
: Maximum input value (10V, or 20mA)
=
18
: Maximum value (100.0%)
=
24
,
25
:
1000x
f749
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......
Page 430: ......