background image

 

TCY-MT-U 

Temperature PID Controller 

 

Doc: 70-00-0176 V1.1, 20100908 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

TCY-MT-U Series Intelligent Temperature Controller 

 

Features 

 

Temperature PID control for HVAC systems.  

 

Up to 2 modulating outputs for DC 0...10V with 10mV resolution.  

 

1 internal temperature sensor and up to 2 external sensor inputs 

 

Multiple remote control functions on external input 

 

Password protected programmable user and control parameters 

 

Blue backlight 

Applications 

 

Various temperature control applications 

 

Stand alone VAV control for pressure independent actuators 

 

Water Only Systems: Radiator, floor heating or chilled ceilings 

 

Individual room control for offices, residential, hotel rooms, 
meeting rooms, etc.  

 
General Description 

The TCY-MT-U is a stand-alone electronic universal controller with one 
temperature control loop. It may use up to 2 PID sequences. The TCY-
MT-U features one internal NTC temperature sensor, up to two external 
sensor inputs and up to two analog outputs. The configuration has been 
reduced to a minimum to allow for a simple and off the shelve usage. 
For more advanced features and current in- and outputs the TCI product 
range is recommended. The TCY-MT-U can be configured using the 
standard operation terminal. No special tool or software is required.  

Name  

 

Ordering 

Item Name 

Item code 

Control Type 

Key-data 

TCY-MT2-U-W1 

40-10 0044-1 

Cooling only 

Compact PID controller with: 
2 TI, 1 AO 

TCY-MT2-U-W2 

40-10 0044-2 

Heating only 

TCY-MT2-U 

40-10 0044 

2-Pipe system 

TCY-MT4-U 

40-10 0046 

4-Pipe system 

1 TI, 2 AO 

Accessories

 

 

 

 

S-Tn10-2 
SD-Tn10-12-2 
SD-Tn10-20-2 
SDB-Tn10-12 
SDB-Tn10-20 
SOA-Tn10 

40-20 0001 
40-20 0002 
40-20 0003 
40-20 0051 
40-20 0004 
40-20 0006 

Flying lead sensor with 2 m cable 
Flying lead duct sensor 12cm immersion depth, 2m cable 
Flying lead duct sensor 20cm immersion depth, 2m cable 
Duct sensor with housing, 12cm immersion depth 
Duct sensor with housing, 20cm immersion depth 
Outdoor sensor 

Selection of actuators and sensors 

Temperature Sensors:  

Use only our approved NTC sensors to achieve maximum accuracy.  Recommended is SDB-Tn10-20 as Duct sensor, SRA-
Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.  

Modulating Actuators:  

Choose actuators with an input signal type of 0-10V DC or 2-10V DC.  

Housing:  

U  = Vertical (2x4”) housing, Standard is square housing 

Function: 

2  = 2 = 2-Pipe, 4 = 4-Pipe

 

Input: 

T  = Temperature, H = Humidity 

Output:  

M  = Modulating, B = Binary 

Series: 

TCY

 

T  C  Y 

-  M 

-  U 

Summary of Contents for TCY-MT2-U-W2

Page 1: ...atures and current in and outputs the TCI product range is recommended The TCY MT U can be configured using the standard operation terminal No special tool or software is required Name Ordering Item N...

Page 2: ...ondensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2MT2 St...

Page 3: ...re used Installation 1 Connect the wires to be connected to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple...

Page 4: ...ndard function If pressed less than 2 sec access for different control modes If pressed for more than 2 sec starts operation level for advanced users Change of time schedules offsets and heat cool set...

Page 5: ...ns Changing of set points may be disabled with UP01 Manually activating heating or cooling mode Pressing the option button for more than three seconds will toggle Heating Cooling mode Manual Heat Cool...

Page 6: ...d in the parameter is displayed immediately 4 Select the parameters with the UP DOWN keys Change a parameter by pressing the OPTION key The MIN and MAX symbols show up and indicate that the parameter...

Page 7: ...roportional part is defined through the p band A narrow P band increases the sensitivity of the controller Typical values used are 1 1 5K for heating 2 3K for cooling sequences The P band should be ex...

Page 8: ...elay the binary contact has to be open before standby mode is activated This function may be used together with key card switches for hotels or motion detectors for offices Auto change over instructio...

Page 9: ...minimum limit on the analog output in cooling mode CP15 and in heating mode CP13 When it reaches this minimum the system is in its dead band and is neither heating nor cooling As the system moves int...

Page 10: ...mode YC1 1 TCY MT2 W2 Heating mode YH1 2 TCY MT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY MT4 Heating and Cooling 4 pipe system YH1 YC1 TCY MT2 0 2 TCY MT4 0 3 TCY MT2 W1 0 TCY MT2 W2 1 TCY MT2...

Reviews: