TCY-MT-U 

Temperature PID Controller 

 

Doc: 70-00-0176 V1.1, 20100908 

© Vector Controls GmbH, Switzerland 

Page 8 

Subject to alteration 

0.2

0.5

1.0

Accuracy in Kelvin, 
Temperature Input 

0 50  100

T °C 

Temperature Input 

The TCY-MT-U includes an NTC-based passive temperature sensor. A 
sensor of the same type can be connected as alternative control input or 
remote control input. The TCY-MT2-U may use an additional input as 
changeover input. The accuracy of the temperature input is shown in the 
table to the right. Specified accuracy can only be guaranteed by using an 
approved temperature sensor. For best results use Sxx-Tn10 sensors.  
 
 

Options for input X1

 

These functions are activated by parameters 
 

External controls input 

The control input is provided by the external input. The internal input will not be 
used.  

Remote Enable 

Opening the external temperature input will force the unit into the OFF operation 
mode. The operation mode cannot be overridden by using the terminal. Connecting 
the binary input to GND returns control of the operation mode to the terminal. This 
function may be used as window contact to prevent loss of energy.  

Toggle of Standby and 
Comfort operation modes 
 

Standby and Comfort modes are controlled through an external contact by connecting 
the external temperature input to ground  

Activation Delay:

 Defines the delay the binary contact has to be open before 

standby mode is activated. 
This function may be used together with key card switches for hotels or motion 
detectors for offices.  

 

Auto change over instructions for input X2 (TCY-MT2 only):  

There are several ways to switch a 2-pipe system from heating to cooling. The temperature of the supply media or the 
outside temperature may be measured. The controller detects the mode automatically. If heating limit is above cooling 
limit, supply media mode is selected. If heating limit is below cooling limit, outdoor mode applies.  
Heating and cooling may be as well changed by an open contact switched to GND. Note: all ground levels of involved 
controllers must be the same in case more than one controller is switched.  
 
Supply media 

Set auto change over limit heating above the change over limit cooling but below the 
temperature of the heating media. For example 25°C (77F).   
Set auto change over limit cooling above the temperature of the cooling media. For 
example 18°C (64F).   

Outside temperature 

Set auto change over limit heating at the temperature where heating should start. For 
example if outside temperature is below 15°C (59F).   
Set auto change over limit cooling at the temperature where cooling should start. For 
example at 25°C (77F).   

Open Contact: heating active 
while contact is closed 

Auto change over limit heating = 25°C (77F) 
Auto change over limit cooling = 15°C (59F) 

Open Contact: cooling active 
while contact is closed 

Auto change over limit heating = 15°C (59F) 
Auto change over limit cooling = 25°C (77F) 

Summary of Contents for TCY-MT2-U-W2

Page 1: ...atures and current in and outputs the TCI product range is recommended The TCY MT U can be configured using the standard operation terminal No special tool or software is required Name Ordering Item N...

Page 2: ...ondensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2MT2 St...

Page 3: ...re used Installation 1 Connect the wires to be connected to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple...

Page 4: ...ndard function If pressed less than 2 sec access for different control modes If pressed for more than 2 sec starts operation level for advanced users Change of time schedules offsets and heat cool set...

Page 5: ...ns Changing of set points may be disabled with UP01 Manually activating heating or cooling mode Pressing the option button for more than three seconds will toggle Heating Cooling mode Manual Heat Cool...

Page 6: ...d in the parameter is displayed immediately 4 Select the parameters with the UP DOWN keys Change a parameter by pressing the OPTION key The MIN and MAX symbols show up and indicate that the parameter...

Page 7: ...roportional part is defined through the p band A narrow P band increases the sensitivity of the controller Typical values used are 1 1 5K for heating 2 3K for cooling sequences The P band should be ex...

Page 8: ...elay the binary contact has to be open before standby mode is activated This function may be used together with key card switches for hotels or motion detectors for offices Auto change over instructio...

Page 9: ...minimum limit on the analog output in cooling mode CP15 and in heating mode CP13 When it reaches this minimum the system is in its dead band and is neither heating nor cooling As the system moves int...

Page 10: ...mode YC1 1 TCY MT2 W2 Heating mode YH1 2 TCY MT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY MT4 Heating and Cooling 4 pipe system YH1 YC1 TCY MT2 0 2 TCY MT4 0 3 TCY MT2 W1 0 TCY MT2 W2 1 TCY MT2...

Reviews: