Type
Error Code
Suggestion
554
1. Log in to the email server or contact the
personnel of the third-party email server to
modify the spam setting rule.
2. Provide ECC run logs and contact the service
center.
550
1. Log in to the email server or contact the
third-party email server personnel to add
the IP address to the whitelist.
2. Provide ECC run logs and contact the service
center.
421
Reduce the email sending speed or contact the
third-party email server personnel to increase
the email server configuration limit.
450
Contact the personnel of the third-party mail
server to add the sender address to the
whitelist and do not limit the sending rate.
451
Provide ECC run logs and contact the service
center to reduce the email sending frequency.
534
Log in to the sender's mailbox client and
enable the access to the insecure applications.
5.5 Commissioning the Smart Busbar
Context
●
In the smart busbar scenario, general input units and power distribution units
communicate with the ECC800-Pro using the Modbus-MAC protocol. After the
general input units and power distribution units properly connect to the
ECC800-Pro, the ECC800-Pro automatically identifies the units.
●
Then, you need to set parameters for the general input units and power
distribution units; otherwise, a false alarm may be generated.
Procedure
Step 1 Set parameters for general input units on the ECC800-Pro WebUI.
1. Set parameters for general input unit 1.
ECC800 Data Center Controller
User Manual