8.7.10 How Can I Set and Add a DC PDF (Modbus-RTU)?
Prerequisites
One end of the straight-through cable has been connected to the RS485/RS232
port on the power distribution monitoring unit in the DC PDF, and the other end
has been connected to the COM port on the ECC800-Pro collector or UIM20A.
Procedure
Step 1 Add a DC PDF (Modbus-RTU).
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add a DC PDF.
Table 8-10 Adding a DC PDF
Path
Parameter
Setting
Choose
System
Settings >
Device
Management
and click Add
Device.
Device
attribute
Select PDU from the drop-down list box.
Device Type
Select TP48202BDCEndCabinet from the
drop-down list box.
Connect To
Select ECC800 from the drop-down list
box.
NOTE
If the other end of the straight-through cable is
connected to the COM port on the UIM20A,
select UIM.
Communicati
ons Port
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the
TP48202B DC end cabinet is connected to the
COM1 port on the ECC800-Pro. If the cabinet is
connected to another port, select the number of
the connected port.
Device
Address
In this example, Device Address is set to
160. During actual configuration, set the
device address for the DC PDF based on
the actual situation.
3. Click Test Connect to check whether the DC PDF is properly connected to the
ECC800-Pro.
–
If the connection succeeds, click Confirm. The connected devices are
displayed in the Number of connected devices list.