Table 5-10 Function commissioning
Item
Alarm Severity
Selection
Description
Associated
alarm severity
Critical
If there is a critical alarm, the
eLight strip light turns on with a
red light.
Critical, Major
If there are multiple alarms, the
eLight strip light preferentially
turns on with a light
corresponding to the high-
severity alarm. After the high-
severity alarm is cleared, the
eLight strip light turns on with a
light corresponding to the low-
severity alarm.
NOTE
● Critical: red light
● Major: orange light
● Minor: yellow light
● Warning: gray light
Critical, Major,
Minor
Critical, Major,
Minor, Warning
None
The eLight strip light is steady
blue (atmosphere light).
NOTE
After you set the alarm severity, the eLight indicator is off if no alarm is generated.
5.7 Commissioning the eLight (for
FusionModule500/800)
When the system type is FusionModule500/800 and an eLight is installed, perform
the following steps to configure it.
Procedure
Step 1 Ensure that the device address of the eLight actuator is the default value 2.
Toggle switches 1 to 4 of the DIP switch specify the device address in binary mode.
ON indicates 1, and OFF indicates 0.
Table 5-11 Setting a device address
Address
Toggle
Switch 1
Toggle
Switch 2
Toggle
Switch 3
Toggle
Switch 4
1
ON
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
ECC800 Data Center Controller
User Manual
5 Power-On Commissioning
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.