6.6.1 FusionModule2000 Linkage Control
Prerequisites
●
You have obtained the IP address of the ECC800-Pro as well as the user name
and password used for WebUI login.
●
A PC with an IP address in the same network segment as that of the ECC800-
Pro is prepared, and the PC has connected to port WAN1 on the ECC800-Pro.
●
Ensure that Enable linkage control function is Yes.
Linkage Grouping
Table 6-38 FusionModule2000 linkage grouping
Linkage Category
Default Status
Function
● Link smoke alarm
with skylight open
● Open door/turn on
lights if smoke
alarm
a
on
If a smoke alarm is raised, the
smart module opens the skylights
and door and turns on lights by
default.
Link smoke alarm with
air conditioner off
off
If this linkage status is set to on
and a smoke alarm is raised, the
smart cooling products shut down
automatically.
Intelligent lighting
a
off
If this linkage status is set to on
and an infrared alarm is raised
when the camera detects human
motion or the door is opened as
authorized, the aisle lights turn on
automatically.
● Link fire control with
skylight open
● Open door/turn on
lights by fire linkage
a
● Link fire control with
air conditioner off
off
If this linkage status is set to on
and a fire occurs in the smart
module, the skylights open, lights
turn on, and the door opens
automatically, or the smart cooling
products shut down automatically.
Link high temperature
with skylight open
off
If this linkage status is set to on,
the skylights open automatically
when a high temperature alarm is
raised and all smart cooling
products fail to communicate with
the ECC800-Pro.