Item
Specifications
Test button
(smoke sensor
test button)
Supports the smoke sensor test.
Hold down the button for 3s to trigger a smoke alarm, and
release the button to stop the smoke alarm.
E-label
Supported
Indicators
Table 3-47 Description of the indicators on the multi-functional sensor
Indicator Color
Name
Status
Description
RUN
Green
Module
running
status
indicator
Blinking at
long
intervals
The multi-functional sensor
successfully registers with
the ECC800-Pro and the
software runs properly (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at
short
intervals
The multi-functional sensor
fails to register with the
ECC800-Pro or the
communication fails (the
indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).
Blinking
The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.
ALM
Red
Alarm
indicator
Steady on
A system failure alarm is
generated.
Off
No system alarm is
generated.
RF_Z
Green
Communicat
ion status
indicator
Steady on
No network parameters
exist, or a network is to be
created.
Blinking at
long
intervals
A network is set up, and no
node access is allowed (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
ECC800 Data Center Controller
User Manual
3 Device Description
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.
55