Table 3-38 LED indicator status
Indi
cato
r
Color
Name
Operat
ion
Status Description
RUN Green
Module
running
indicator
/
Blinki
ng
● The door lock is paired
with the host, and the
power supply is normal:
The indicator blinks at
0.5 Hz (on for 1s and
then off for 1s).
● The door lock fails to
pair with the host: The
indicator blinks at 4 Hz
(on for 0.125s and then
off for 0.125s).
Off
The power supply is
abnormal.
Press
SW.
Blinki
ng
interm
ittentl
y at
super
short
interv
als
● The indicator blinks at
super short intervals for
0.5s, and then off for
0.5s.
● The indicator blinks at
super short intervals
(blinking at 10 Hz, on for
0.05s and then off for
0.05s). The cycle lasts for
5s.
ALM Red
Alarm
indicator
/
Stead
y on
A system failure alarm is
generated.
Off
The system is normal.
3.2.5 Smart Module Actuator
The smart module actuator is applied in a smart module. It controls the lighting
inside the smart module through the access control system, host instructions,
infrared linkage information (disabled by default), or lighting button, and provides
a pad charging port. The smart module actuator can also control the rotating
skylight of the aisle based on the fire alarm linkage information or the host
control information, and opens the magnetic lock when detecting the card swiping
information of the card reader, exit button information, and fire linkage
information. In addition, the smart module actuator manages access rights,
records entrance and exit events, and records alarms.
ECC800 Data Center Controller
User Manual
3 Device Description
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.
44