Table 3-71 T/H sensor specifications
Item
Specifications
Temperature measuring range
–20°C to +70°C
Temperature accuracy
±1°C
Humidity measuring range
5%–95% RH
Humidity precision
±5% RH (25°C, 20%–80% RH)
Operating temperature
–20°C to +70°C
Operating voltage
9–16 V DC
Storage temperature
–40°C to +70°C
Output
RS485
3.2.20 Infrared Remote Control Module
Figure 3-44 Infrared remote control module
Table 3-72 Technical specifications of the infrared remote control module
Item
Specifications
Number of supported
remote control
commands
≤ 4
Communication
Interworks with the monitoring system over
Modbus-RTU to implement remote control.
The baud rate can be 9600 bit/s.
ECC800 Data Center Controller
User Manual
3 Device Description
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.
75