Figure 3-30 WLDS600 water sensor
(1) Tie line
(2) Water leakage location
cable
(3) Terminal
(4) Extension line
(5) Water leakage locator
-
Table 3-56 Technical specifications of the WLDS600 water sensor
Item
Specifications
Dimensions (L
x W x H)
70 mm x 58 mm x 86 mm
Power supply
9–16 V DC or 9–16 V AC
Impulse
current
≤ 450 mA
Power
dissipation
< 2 W
Power,
communicatio
n connector
RJ45 female connector 1 piece
Protocol type
Modbus-RTU, data bits 8 bits, no parity
Baud rate,
address
Default support 9600, baud rate configurable, address
configurable, default address is 1, stop bit is 1 bit.
Detected
distant
100 m (support cable connection in series)
ECC800 Data Center Controller
User Manual
3 Device Description
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.
62