Table 8-11 Remote door opening
Path
Setting
Monitoring > Aisle >
Smart Module Actuator
Group > Smart Module
Actuator n > Controls
Select Remote door opening and click Submit
CA UTION
● Remotely opening the door may open the smart module door, and this may
pose security risks. Exercise caution when performing this operation.
● Remotely opening the skylight may open the smart module skylight, and this
may pose security risks. Exercise caution when performing this operation.
----End
8.7.13 How Can I Set and Add a PDU8000 (Modbus RTU)?
(C41)
Prerequisites
One end of the straight-through cable has been connected to the COM port on
the PDU8000, and the other end has been connected to the COM port on the
ECC800-Pro collector or ETH converter.
Procedure
Step 1 Set the PDU8000 monitoring parameters.
1. Enter the PDU8000 home screen and tap System Info.
2. Choose System Info > Settings, enter the user name admin and password
000001, and tap
. In the displayed dialog box for confirming the
password, tap Confirm.
3. Tap Communication to access the PDU8000 communication settings screen
and set IP address assign to Manual. Set Serial port baud rate to 9600, and
Serial port address to 1.
ECC800 Data Center Controller
User Manual
8 FAQ
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.
316