NO TE
The settings in the following table are used as examples to describe the basic configuration.
Table 6-53 Basic configuration
Parameter
Setting
Description
Device Name
IT Cabinet
101
Set based on the actual device
name.
Cabinet height
42
U space quantity of the
cabinet.
Cabinet width
600
The width of the cabinet.
Power
Distribution
Parameter
Settings
Power system Single-phase
Set single-phase or three-
phase based on the actual
power supply.
Number of
power
supplies
2
rPDU quantity.
Rated cabinet
power
6.00
Set based on the actual rated
power of the cabinet.
rPDU-A01
PDU80001 >
1QF1(L1)
Select a power distribution
device and power distribution
branch for the rPDU
numbered rPDU-A01 in the
cabinet.
rPDU-B01
PDU80001 >
2QF1(L1)
Select a power distribution
device and power distribution
branch for the rPDU
numbered rPDU-B01 in the
cabinet.
Branch auto-fill mode
● Ascending
order
● Descendin
g order
● Ascending order: If the
branch for the first cabinet
is 1QF1(L1), 2QF1(L1), the
branches for subsequent
cabinets are 1QF2(L2),
2QF2(L2), and the like.
● Descending order: If the
branch for the first cabinet
is 1QF10(L1), 2QF10(L1),
the branches for
subsequent cabinets are
1QF9(L3), 2QF9(L3), and
the like.