Table 8-48 Description of communications parameters to be set on a device
Parameter
Recommended Value
Baud rate
This section uses 9600 as an example. Set this
parameter based on site requirements.
NOTE
For certain devices, this parameter does not need to be set.
Communications
address
This section uses 1 as an example. Set this parameter
based on site requirements.
Step 2 Add the device to the ECC800-Pro WebUI.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add the device.
Choose System Settings > Device Management and click Auto Discover
Device to add the device. The device connection information is displayed.
Figure 8-33 Device connection
----End
8.32 How Can I Add a Dry Contact Device Connected to
the ECC800-Pro Through a UIM20A Expansion Module?
Prerequisites
This section uses the device (such as a door status sensor) connecting to the AI/
DI_3 port on the UIM20A expansion module as an example.
Context
Each UIM20A expansion module supports a maximum of eight dry contact
devices. In the scenario with multiple UIMs in the same smart module, a
maximum of 48 dry contact devices can be connected.
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Add the device.