8.7.5 How Can I Set and Add a UPS5000 (Modbus-TCP)?
Prerequisites
One end of the straight-through cable has been connected to the FE port on the
UPS5000 and the other end has been connected to the PoE port on the smart ETH
gateway.
Procedure
Step 1 Set the UPS5000 monitoring parameters.
1. Enter the UPS5000 home screen and tap System Info.
2. Choose System Info > Settings, enter the user name admin and password
000001, and tap
.
3. Tap Comm. Settings and choose IP Settings. Set IP address allocation to
Automatic (DHCP) on the displayed communication settings screen and the
UPS5000 is discovered by ECC800-Pro automatically and is connected to the
ECC800-Pro.
NO TE
On the ModbusTCP Settings screen, set ModbusTCP encryption to Enable.
----End
8.7.6 How Can I Set and Add a PDU8000 or Integrated PDU
(over Modbus-TCP)?
Prerequisites
One end of the straight-through cable has been connected to the FE port on the
PDU8000 or integrated PDU, and the other end has been connected to the PoE
port on the smart ETH gateway.
Context
The method of connecting the PDU8000 to the ECC800-Pro is the same as that for
the integrated PDU. Connecting the integrated PDU to the ECC800-Pro by
following the instructions in this section.
Procedure
Step 1 Set the PDU8000 monitoring parameters.
1. Enter the PDU8000 home screen and tap System Info.
2. Choose System Info > Settings, enter the user name admin and password
000001, and tap
.
3. Tap Communication to set IP address assign to Automatic(DHCP) on the
displayed communication settings screen and the PDU8000 is discovered by
ECC800-Pro automatically and is connected to the ECC800-Pro.