6.5.3.1 Commissioning an IPC6325 Camera
Prerequisites
●
If multiple cameras are accessed, retain the connection of one camera and
disconnect connections from other cameras. After commissioning the
connected camera, commission other cameras in the same way.
●
The camera has connected to the smart ETH gateway and the smart ETH
gateway communicates properly with the ECC800-Pro.
●
The camera software version is later than V500R019C30.
Context
●
Before commissioning the IPC6325 camera, set the IP address for the IPC6325
camera based on customer requirements.
●
Configure the internal IP addresses of the camera and VCN or IVS1800 and
the IP address of the LAN port on the ECC800-Pro in the same network
segment.
●
Configure the external IP addresses of the camera and VCN or IVS1800 and
the IP address of the WAN1 port on the ECC800-Pro in the same network.
●
Set the internal and external IP addresses as planned by the customer. The
following IP addresses are for reference only.
Table 6-20 IP address planning
Device
Internal IP Address
External IP Address
Camera
Example: 192.168.248.50; range:
192.168.248.50–192.168.248.199
Camera external IP
address
NOTE
The 192.168.246.X
network segment
cannot be set.
VCN/
IVS1800
Example: 192.168.248.51; range:
192.168.248.50–192.168.248.199
VCN or IVS1800
external IP address
NOTE
The 192.168.246.X
network segment
cannot be set.
Procedure
Step 1 Log in to the camera web system and enable ONVIF.
1. Remove the network cables that connect the smart ETH gateway to the LAN1
and LAN2 ports on the ECC800-Pro.
2. Use a network cable to connect the PC to the PoE port on the smart ETH
gateway. Then, set the local IP address of the PC to 192.168.0.11.
3. Remove the camera shell and press the reset button for 6s to 10s to restart
the camera.