Table 6-68 Other parameters
Signal Name
Signal Value
Description
Synchronize system
time to device
Enable/Disable
Whether to synchronize the
system time to devices that
support time synchronization.
After this function is enabled, the
ECC synchronizes time parameters
to devices that support time
synchronization every 4 hours.
Upgrade package
signature verification
Enable/Disable
Indicates whether to use the
upgrade package signature
verification function.
Communication port
status
Displayed/Not
displayed
Indicates whether to display the
communication port status of the
access actuator, skylight actuator,
FusionModule Actuator, and multi-
functional sensor.
Alarm convergence
enable
Enable/Disable
Indicates whether to use the alarm
convergence function. After this
function is enabled, only root
alarms are reported.
Key update interval
30–1095 days
Set the interval for automatically
updating the key.
SNMP
Enable/Disable
Indicates whether to use the
SNMP communication port.
RSTP
Enable/Disable
Indicates whether to use the RSTP
communication port.
Transparent
transmission channel
port
Enable/Disable
Indicates whether to use the
transparent transmission channel
port.
SSH
Enable/Disable
Indicates whether to enable login
to the ECC over SSH.
Cascading port
Enable/Disable
Indicates whether to use the
cascading port.
High-density island
solution
Yes/No
Indicates whether to enable the
high-density island solution.
Manually updating a
key
Yes
The system provides the automatic
key update function. Manual
update is required only if the key
is disclosed. Select the parameter
and click Submit.
ECC800 Data Center Controller
User Manual
6 Feature Description
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.
274