Table 3-1 ECC800-Pro environmental specifications
Item
Specifications
Operating
temperature
–20°C to +50°C
Storage temperature
–40°C to +70°C
Relative humidity
5%–95% RH (non-condensing)
Altitude
0–4000 m (When the altitude is between 3000 m and
4000 m, the temperature decreases by 1°C for each
additional 200 m.)
Table 3-2 ECC800-Pro structural specifications
Item
Specifications
Dimensions (L x W x H)
442 mm x 330 mm x 43.6 mm
Weight
7.5 kg (dual power su main
control module)
Color
Black
Installation requirements
Can be installed in a 1 U space in a
standard 19-inch cabinet
Environmental protection
RoHS5, REACH, WEEE
Figure 3-2 ECC800-Pro (rear view)
(1) 53.5V DC_OUT1
(2) 53.5V DC_OUT2
(3) AC_INPUT1
(4) AC_INPUT2
-
-
Power Port
The ECC800-Pro provides four power ports, including two AC input ports
(AC_INPUT1 and AC_INPUT2) and two DC output ports (DC_OUT1 and
DC_OUT2).
provides the power port pin definitions.
ECC800 Data Center Controller
User Manual
3 Device Description
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.