Step 5 Choose Monitoring > System > Robot IPC > Running Information to view the
running information about the robot IPC. Choose Running Parameters and
Controls to verify functions.
Figure 6-117 Robot IPC
Tab
Parameter
Description
Runni
ng
Infor
matio
n
-
Views the running information about the robot IPC.
Runni
ng
Para
meter
s
Device name
Specifies the display name of the IPC.
Move speed
Specifies the movement speed of the IPC.
Alm battery
threshold
If the battery level is lower than the value of this
parameter, the robot reports an alarm.
Charge
battery
threshold
If the battery level is lower than the value of this
parameter when an automatic inspection task is being
executed, the robot automatically returns to the
charging pile for charging.
Robot moving
timeout
threshold
If the robot does not reach the target point for
inspection within the time specified by this parameter,
the task times out and the next inspection task starts.
PTZ max
height
If the PTZ height is set, the robot performs limit
control. This parameter specifies the maximum height
of the PTZ.
PTZ camera
focus mode
Specifies the camera focus mode: automatic or manual.
Contr
ols
Rotate angle
Specifies the body angle.
Auto return
Controls the robot to return to the charging pile for
charging.
Robot IPC
reboot
Robots the robot IPC.
Robot IPC
alarm clear
Clears robot IPC alarms.
Fill light
control
Turns on or off the illuminator on the PTZ camera.
ECC800 Data Center Controller
User Manual
6 Feature Description