Follow-up Procedure
View the power supply and distribution link diagram of the power module on the
NetEco. If the device sequence in the link diagram is inconsistent with the actual
physical device position, adjust the device No.
6.19 Intelligent Networking of FusionModule2000
Busways
Prerequisites
●
Busway devices have been connected to the ECC800-Pro.
●
The FusionModule2000 plan view has been created, and the device positions
in the plan view are consistent with actual positions.
Context
By identifying the MAC address set of adjacent ports of busway devices, the
system automatically identifies the link relationship and implements intelligent
networking of busways.
NO TE
● The link relationship can be automatically identified only when the software version of
both the general input units and power distribution units of busways is V304 or later.
● When a dense busway connector box (equivalent to the general input unit in functions)
is used, the dense busway connector box is connected to ports COM1–COM4 on the
UIM20A expansion module. The Modbus protocol addresses of the corresponding
devices are 1–4. Devices need to be manually added.
Procedure
Step 1 Go to the FusionModule2000 view, click Modify Device, select any general input
unit or power distribution unit, and click Automatic identification.
NO TE
You can set Power supply branch to manually change the link relationship.
ECC800 Data Center Controller
User Manual
6 Feature Description