Path
Parameter
Setting
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
Device Type
Select PDU2000-M (C) or PDU2000-M (H)
from the drop-down list box based on the
actual device.
Connect To
Select ETH Converter1 from the drop-
down list box.
NOTE
In this example, the PDU2000 is connected to
ETH converter 1.
Communicat
ions Port
COM1/COM2
Device
Address
Enter the actual device address of the
PDU2000.
3. Click Test Connect to check whether the PDU2000 connects to the ECC800-
Pro properly.
–
If the connection succeeds, click Confirm. The connected devices are
displayed in the Number of connected devices list.
–
If the connection fails, check whether the cable is properly connected to
the device, whether the device is running properly, and whether the
parameter settings are consistent with the device parameters.
----End
5.9 Commissioning Cabinet Electronic Clasp Locks
If a cabinet electronic clasp lock is installed, perform the following steps to
configure it.
Prerequisites
●
COM1–COM3 on the ECC800-Pro are connected to cabinet electronic clasp
locks.
●
The smart module view has been deployed. The layout type is single-row
view.
●
The cabinet door can be opened and closed properly. If the cabinet door
cannot be opened and closed properly, adjust the position of the cabinet
electronic clasp lock by performing steps 1 and 2.
Procedure
Step 1 (Optional) Check whether the cabinet door lock is leveled to 2000 (+3) mm. If
not, adjust it.
Step 2 (Optional) If the cabinet door still cannot be opened after step 1 is performed,
adjust the position of the cabinet electronic clasp lock by using the slotted holes
until the cabinet door can be opened and closed properly.
ECC800 Data Center Controller
User Manual
5 Power-On Commissioning
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.
123